Amperage is the number everyone checks. It is printed large on the handle, it is the first field in every catalogue, and it is what most people mean when they say two breakers are the same. But the continuous current rating only tells you what the breaker carries on a normal day. The interrupting rating tells you whether it survives the worst one.
What the interrupting rating means
The interrupting rating, often written as AIC or kAIC, is the highest fault current a breaker is tested to interrupt safely at its rated voltage. It is published in kiloamps: 10kA, 14kA, 22kA, 65kA and so on.
When a short circuit happens, the current through the breaker is no longer limited by the load. It is limited only by the supply and the wiring, and it can be thousands of amps. A breaker asked to clear more fault current than it is rated for may fail to interrupt it, and can be destroyed in the attempt.
Two 20A breakers can look identical and still be rated 10kA and 65kA. On a normal day you cannot tell them apart. During a fault, you can.
Available fault current decides what you need
The rating you need depends on the available fault current at the point where the breaker is installed. That figure is set by the supply transformer, its impedance, and the length and size of the conductors between it and the panel. It is highest close to the service and drops further downstream.
In North America, the National Electrical Code requires equipment intended to interrupt current at fault levels to have an interrupting rating at least equal to the available fault current at its line terminals (NEC 110.9). Many service panels are labelled with the available fault current for exactly this reason.
Interrupting rating is not SCCR
The two terms are easy to mix up:
Interrupting rating belongs to the protective device itself: the breaker or fuse that opens the circuit.
Short-circuit current rating (SCCR) belongs to the equipment or assembly: the panelboard, control panel or motor controller as a whole.
A panel can only claim its SCCR when it is built with the devices it was rated with. Swapping one breaker for another with a lower interrupting rating can lower the rating of the whole assembly.
Series ratings are a combination, not a part
Some installations use series-rated combinations, where an upstream device helps a downstream breaker handle a fault larger than the downstream breaker could interrupt alone. That rating applies only to the tested and listed combination. Replace either device with one that is not part of the listed combination and the series rating no longer applies, even if the amperage and frame match.
What to check when you substitute a breaker
Interrupting rating at the right voltage. Ratings are often published at more than one voltage, and the figure at 480V is usually lower than at 240V. Compare like with like.
Equal or higher than the original. A replacement should never bring a lower interrupting rating than the part it replaces.
Enough for the available fault current. If you do not know the available fault current at that panel, find out before you sign off.
Series-rated installations. If the panel relies on a series rating, the replacement must be part of the same listed combination.
The right standard. A UL interrupting rating and an IEC Icu or Ics are not the same measurement, so they cannot be compared number for number.
The short version
Amperage tells you the breaker fits the load. Interrupting rating tells you it is safe for the installation. A substitute has to match both.
When you cross-reference a breaker, compare the interrupting rating as carefully as the amperage. If the original's rating is unclear, check the manufacturer's datasheet for that exact catalogue number before you choose a replacement.